DE-18 USER MANUAL SECTION 5
68
S NUMBER SETTINGS (CODE 64)
“S” Number Description Range Default Setting
S-0 Circle=exit
S-1 Line 1 select
I1-4 XXXX
I5-12 XXXX
XXXX
O1-7 XXXX XXX
S-2 P2 offset
100-300 SPSI 0
S-3 P2 Max
0-500 PSI 200
S-4 Drain open
0-20 Sec
3
S-5 Drain close
0-600 Sec
120
S-6 Drain on STP
0-999 Sec
10
S-7
SETUP LKOUT
Setting this to YES will prevent starting while making
Sequencing Setups. It will default to NO on power-down
and power-up.
NO/YES
--
S-8
SLV COM SEL
The Slave’s Address or the Master’s # of Slaves.
independent/SLV1/
SLV2/.../SLV9
Independent
S-9
MASTR COM EN
The Master of Slaves Enable
NO/YES
NO
S-10 DEMAND INCR
-10.0-110.0%
80.0
S-11
DEMAND “+” D
This is the Delay observed between starting the next unit.
0-1000 Sec
60
S-12 DEMAND DECR
-10.0-110.0%
20.0
S-13
R UNLD PRS
This is the pressure that is relative to the Setpoint
Pressure where the Unload is allowed. For operation see
body of the sequence.
0-20 PSI
5
S-14
R LOAD PRS
This is the pressure that is relative to the Setpoint
Pressure where the Load is allowed. For operation see
body of the sequence.
0-20 PSI
5
S-15
P2 OVRD STRT
This is the pressure during a slave communications
failure that a Slave will automatically start at.
75-135 PSI
75
S-16
CAT COM SD#
This is a counter that counts the number of “no data”
packets into the MDDM to the EMS before a CAT COM
SD is active.
0-20 Packets
15
S-17
POWER DOWN DELAY
This is a counter that counts the number of “no data”
packets into the MDDM to the EMS before a CAT COM
SD is active.
0-999 Seconds
300
S-18
CAT SD COUNTER
This is a counter that counts the number of processor
cycles that the RPM must be below the CAT SD RPM set
point in order to process the CAT SD.…
0-5
4
S-19
ECM COMM LOCKOUT
This is the number of seconds after the ECM is powered
before we start to look for valid data from the ECM.
0-60
17