EasyManua.ls Logo

Sullair RD-3800-460-60-A - RN & RD Series Refrigerated Non-Cycling Air Dryers; Introduction and Specifications

Sullair RD-3800-460-60-A
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 3
41
PRODUCT USER MANUAL
RN & RD SERIES REFRIGERATED NON-CYCLING
COMPRESSED AIR DRYER
3.1 INTRODUCTION
The Sullair Non-cycling Refrigerated air dryers are
designed for constant full load operation. They use
specially designed heat exchangers with integrated
components to provide consistent dewpoint and
trouble-free service for years to come.
The dryers remove the moisture, oil vapors and other
harmful contaminants from the compressed air
stream. By using basic refrigeration, the hot
saturated air is cooled in the highly efficient heat-
exchangers and the moisture is condensed and
removed. Additional filtration eliminates other
contaminants and particles.
Water (moisture) is one of the greatest enemies of air
tools and piping. Left untreated in the compressed air
stream, this moisture will deteriorate the tools,
equipment and piping with corrosion, pipe scaling,
freezing and a host of other problems that will
diminish the life of your entire compressed air
system. With a Sullair refrigerant dryer, you can be
assured of clean, dry air with consistent dewpoint
between 36-40°F. The unique three-in-one heat
exchanger combination—
Air to Air (pre-cooler/re-heater Heat Exchanger)
Air to Refrigerant (high efficiency Heat
Exchanger)
Integrated Separator (located at the coldest point
to maximize moisture extraction)
heats up the exiting air, thereby eliminating the
chances of freezing even in relatively cooler ambient
conditions. Warm dry air will not affect the piping nor
the tools and the result is extended tool life. In
addition, applications that require clean dry air can
rely upon Sullair’s non-cycling refrigerated air dryers
to provide dry air at full load continuously.
3.2 SPECIFICATIONS
Pay attention to the Minimum and Maximum
operating conditions before installing and operating
the dryer.
If your application does not match the above criteria,
contact your Sullair distributor and they will be able to
provide the right dryer for your application.
Normal Operating Pressure 100 PSIG
Normal Operating Temperature 100°F
Normal Ambient Temperature 100°F
Maximum Operating Pressure 230 PSIG
Minimum Operating Pressure 75 PSIG
Maximum Ambient Temperature 120°F
Minimum Ambient Temperature 40°F
Maximum Operating Temperature 150°F

Table of Contents