EasyManua.ls Logo

Sullair SRL-250 - Inputs; Outputs

Sullair SRL-250
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SRL Service Manual
Revision 00
July 2007
Page 23 of 56
4.2.1 Inputs
Consists of both analog inputs (J2) and digital inputs (J1 & J3).
Analog Inputs (J2)
J2 1 GND Ground for temperature sensors.
J2 2 B1 Dewpoint Temperature Sensor (B1)
J2 3 B2 Evaporator Temperature Sensor (B2)
J2 4 B3 Compressor Discharge Temperature Sensor (B3)
J2 5 B4 Optional Temperature Sensor
Digital Inputs (J1 & J3)
J1 1 ID5 Low Pressure Switch (LP Alarm)
J1 2 0V Power (Ground)
J1 3 24V Power (24Vac)
J1 5 ID1 High Pressure Switch (HP Alarm)
J1 8 ID2 Compressor Protection (CP Alarm)*
J1 11 ID3 Remote On-Off
J3 1 IDC2 Common (Ground)
J3 2 ID4 Drain Level Sensor**
J3 3 +5V Power Input to Drain Level Sensor**
* SRL-1600 to 6000 (60Hz) and SRL-630 to 1800 (50Hz) only.
** SRL-325 to 6000 (60Hz) and SRL-120 to 1800 (50Hz) only.
4.2.2 Outputs
All outputs are digital.
Digital Outputs (J1 & J3)
J1 4 NO1 Compressor Contactor (KM1) & Liquid Line Solenoid Valve (YV1)
J1 6 C4 Common Alarm
J1 7 NO2 Hot Gas Bypass Solenoid Valve (YV2)
J1 9 NO4 Alarm/Warning (N/O) Contact
J1 10 NO3 Drain Solenoid Valve (YV3)
J1 12 NC4 Alarm/Warning (N/C) Contact

Table of Contents