TMSL 097-44018-26 Issue 2: Sep 99
Page 88
COMMAND CODE: RTRV-COM-CONN
PURPOSE
RETRIEVE COMMUNICATION CONNECTION
This command displays the connection status of the shelf.
INPUT FORMAT
RTRV-COM-CONN:[<tid>]:<aid>:<ctag>;
aid = SHELF
RESPONSE FORMAT
<sid> <date> <time>
M <ctag> COMPLD
"<aid>" ...
/*
COM-1=<value>[,ACT-USER=<uid>],
COM-2=<value>[,ACT-USER=<uid>],
COM-3=<value>[,ACT-USER=<uid>]
*/
value = status of communication port (ACTIVE or INACTIVE)
uid = the user id (as set by the ENT-USER-SECU command) of the user
logged onto the port
Notes:
1. The “,ACT-USER= <uid>” part of the response appears only if the communication port is active and
security is enabled by section 4 of switch SW1 on the MIS card.
2. A status of INACTIVE (even if the port is active) will be reported for any communication port that is
using a 3-wire connection or has been set for a comtype of TERM1 with the ED-COM command.

Table of Contents

Other manuals for Symmetricom TimeProvider 500 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 500 series and is the answer not in the manual?

Symmetricom TimeProvider 500 series Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 500 series
CategoryData Loggers
LanguageEnglish

Related product manuals