EasyManua.ls Logo

Symmons TempControl HTA-100 - User Manual

Symmons TempControl HTA-100
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
■ Connect 120 VAC line voltage to the primary side of the
transformer as displayed in Figure 1.
12V
6V
T
coil
connections
Relay 12 VDC @ <80mA
(customer supplied option)
Remote monitoring
system connections
Temperature probe and
1/4" NPT male tting
Water hammer
arrestor (optional)
Tee tting
(required, see
options)
Alarm
control
module
Water ow
Transformer
12 VAC/15 VA
Solenoid valve (optional)
12 VDC, 10 Watts max
120 VAC Power
25'probe cable
(optional lengths)
■ Connect the 12 VAC secondary side of the transformer to
the 12 VAC power input terminals on the back of the alarm
control module as identied in Figure 2 below. Note that
there is no polarity required for the input terminals.
ON
OFF
Fuses #229
1.5A / 250VP
12 VAC
power input
12 VDC valve
power output
(optional)
Temperature
input probe
DIP Switches
Rear view of Alarm Control Module
12 VDC relay
power output
(optional)
■ Temperature Probe - Plug probe into the connector on
the backside of the control module as identied in Figure2
above. Note that the connectors are keyed and will only mate
in one direction. (optional cable lengths are available)
■ Solenoid Valve (optional) -
Connect coil wires between the
solenoid valve and the valve power output terminals on the
back of the control module as identied in Figure 2 above.
Note that there is no polarity required between connections.
High Temperature Audio Visual Alarm System, HTA-100
Installation and Service Instructions
TempControl
®
General Information
■ Alarm System - TempControl High Temperature Audio
Visual Alarm System will monitor, alert and alarm when
water temperature exceeds preset limit. It best ts
applications where there is a critical need to accurately
monitor and control warm or hot water temperature.
■ Solenoid Valve (optional) - When alarmed, the valve is
de-energized and closes to provide complete shutdown of
the water ow.
■ Relay (customer supplied option) - Installed relay enables
remote monitoring of alarm control module.
■ Caution Set Point - is the lower of the two set point
temperatures that alerts when the output water is
approaching an undesirable temperature limit.
■ Alarm Set Point - Once the output temperature reaches the
alarm set point, the system goes into full alarm mode.
Installation
Important: All piping should be thoroughly
ushed prior to installation to prevent debris from
interfering with the solenoid operation. Do not run
solenoid power and temperature probe through
same conduit.
Piping
■ Tee Fitting - Required; appropriate size tting for
application purchased seperately (see options).
■ Temperature Probe - Locate probe as far downstream from
mixing valve as is reasonably possible.
a. Slide connector nut and ferrule piece over the probe.
b. Slide probe 1/2” to 2/3” into the tee tting.
c. Slide the ferrule and connector nut down the probe sha
and tighten in place.
■ Solenoid Valve (optional, 12 VDC, 10 Watts, normally
closed) - Install valve directly before the temperature probe in
any orientation. Make note of the correct direction of the water
ow as marked on the valve.
Electrical
■ Mount the 4" x 4" supplied mounting box in a dry location
within wiring reach of the temperature probe and solenoid
valve if used.
■ Mount supplied transformer.
(120 VAC – 12 VAC/15 VA UL listed, CSA certified class 2)
Figure 1
Figure 2
For California Residents
WARNING: is product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
Question and Answer IconNeed help?

Do you have a question about the Symmons TempControl HTA-100 and is the answer not in the manual?

Symmons TempControl HTA-100 Specifications

General IconGeneral
BrandSymmons
ModelTempControl HTA-100
CategorySecurity System
LanguageEnglish