Explanations
Cooling
recovery
Cooling
recovery
No
Coolinglimit:
2.0°C
SetthecoolingrecoverytoYes
orNo.
Setthecoolinglimit(the
differenceintemperature
betweenextractairandoutdoor
airthatactivatesthecooling
recovery).
External
setpoint
External
setpoint
Notactive
Minsetp.:
12.0°C
Maxsetp.:
30.0°C
Anexternalsetpointdevicecan
beconnected.Thesetpoint
devicemustfollowthePT1000
resistancecurve.Thesetting
rangecanberestricted.
Alarmsettings
Alarm
no(1–100):1
RunError
SupplyAir
Communication
FunctionPort1
Slave
FunctionPort2
Slave
Choosebetweendifferent
communicationsSlave,
Expansionunit,
Frequencyconverter,
Externaldisplay,Exp
andfreqconvorExpand
extdisplay.
SMS:Notactive
Nbr1:
Nbr2:
Nbr3:
Accessrights
LogonLogon
Enterpassword
xxxx
Actuallevel:
None
Logontoservicelevelby
enteringa4-digitcode.After
reachingthedesiredlevelgo
backwith“LEFT”arrow(press
2times)onthecontrolpanel.
Standardcodefromfactory
toenterservicelevelis2222.
Backtooperatorlevel:1111
LogoffLogoff?
No
Actual
level:None
LogofffromAdministratorlevel
bychangingNotoYeswiththe
"OK"and"UP/DOWN"buttons
Automaticlogoffafter6minutes
ofinactivity.
Change
password
Changepassword
for
level:None
Newpassword
xxxx
Setanewpasswordforthe
levelofyourchoice.
Canonlybedoneoncelogged
ontotheservicelevel.
TopvexSR/TR03,SR/TR04,SR/TR06OperationandMaintenanceInstructions
206902
22
SystemairAB

Other manuals for SystemAir Topvex SR03

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Topvex SR03 and is the answer not in the manual?

SystemAir Topvex SR03 Specifications

General IconGeneral
BrandSystemAir
ModelTopvex SR03
CategoryAir Handlers
LanguageEnglish

Related product manuals