EasyManua.ls Logo

TECATOR Soxtec System - INSTALLATION; CONNECTION

TECATOR Soxtec System
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION
Place the units on a laboratory bench. Depending on the sol-
vent you are going to use, the Extraction Unit might be locat-
ed in a fume cupboard separated from the Service Unit.
As an alternative there is a connection on the rear of the Ex-
traction Unit which can be connected via fiexibie tubing to a
ventilation fan. The Extraction Unit must be placed close to a
cold water tap and drainage.
111:1. CONNECTION
Connect the PVC-tubing (0 8/11 mm) for cold water according
tofig. B.
Connect the insulated rubber tubing for hot water according
to f ig. B. Make sure that the rubber seals are on place. (Fig. C)
It is enough to fasten the connection by hand.
The Service Unit must be placed close to a wall socket. Never
connect it without water in the tank. Connect the hot water
tubing from the Extraction Unit and the PVC-tubing for air.
Seefig. B.
If necessary the Extraction Unit can be placed further away
from the Service Unit (standard length of the hot water tubing
is 3 m). For this purpose the 1000-1460 extension kit should
be used.
If you are going to connect an additional Extraction Unit use
the 1000-1461 assembly kit.
r
r
Fig. B
1. Cold water inlet for con-
densers (water flow 1—2 1/
min.)
2. Water outlet from conden-
sers
Hot water connections: 7 con-
nected to 3 and 8 connected
to4
Air tubing connection: 6 con-
nected to 5
9. Electrical cable
1 2
6 o
70
8 O
O9
3
O
4
O O
5
o