MCW2B5XAB MPW2B5XAA
Power source
Performance
Input kW
Running Amps A
Total cooling capacity (1) High/Med./Low
kW
Sensible cooling capacity (1) High/Med./Low
kW
Heating capacity (2) High/Med./Low
kW
Air circulation High/Med./Low m³/h
Features
Controls/Temperature controls
Control unit
Timer
Fan speed
Airflow direction Horizontal
Vertical
Water capacity in cooling
High/Med./Low
l/h
Pressure drop on water in cooling (1)
High/Med./Low
kPa
Pressure drop on water in heating (2) High kPa
Air Filter
Power noise level High/Med./Low dB-A
Water tubing connections
Air clean filter
3-Way valve + By-pass (1/2 gas male, KVS 1,6, 230 NC)
Dimensions & Wei
g
ht
Package dimensions Height mm
MCW
Width mm
Depth mm
Shipping volume
m
3
Package dimensions Height mm
MPW
Width mm
Depth mm
Shipping volume
m
3
Weight Net kg
Shipping kg
DATA SUBJECT TO CHANGE WITHOUT NOTICE
(1)
Air inlet 27°C (D.B.) / 19°C (W.B.); Water inlet 7°C; Water outlet 12°C
(2)
Air inlet 20°C; Water inlet 50°C (same water capacity as in conditions (1))
OPERATION LIMITS
Min. water inlet temperature 4°C Min. air recirculation temperature 5°C
Max. water inlet temperature 60°C Max. air recirculation temperature 32°C
Max. operating pressure of hydraulic circuit 16 bar
0,11
273
0,075
8.0
27,2/---/9,7
26,2
Manual
Auto
290/---/165
855
11,0
233
0,064
322
855
230 V - 50 Hz
Wireless remote control unit
Microprocessor/ I.C. thermostat
1,67/---/0,96
1,30/---/0,74
2,38/---/1,49
270/---/180
0,020
ON/OFF 24 hours
3 and Auto
322
Washable, polypropylene, class HB (UL94)
45/--/35
1/2" gas female
Optional
Optional
4