02 - IM Motor Parameter Group
02- 00
No-load current of motor 1
Range
【0.01~600.00】A
02- 01
Rated current of motor 1
Range
Modes of V/F、V/F+PG are 10%~200% of inverter’s rated current. Modes of SLV、
SV are 25%~200% of inverter’s rated current.
02-03
Rated rotation speed of motor1
Range
【0~60000】rpm
02- 04
Rated voltage of motor1
Range
220V:【
50.0~240.0】V
440V: 【
100.0~480.0】V
02- 05
Rated power of motor 1
Range
【
0.01~600.00】KW
02-06 Rated frequency of motor 1
Range
【
10.0~400.0】Hz
【
10.0~1200.0】Hz (when 00-31 = 1)
02-07 Pole of motor 1
Range
【2,4,6,8】
02-09 Excitation current of motor 1
Range
【10.0~100.0】%
02-10 Core saturation coefficient 1 of motor 1
Range
【0~100】%
02-11 Core saturation coefficient 2 of motor 1
Range
【0~100】%
02-12 Core saturation coefficient 3 of motor 1
Range
【80~300】%
02-13 Core loss of motor 1
Range
【
0.0~15.0】%
02-15 Resistance between wires of motor 1
Range
【0.001~60.000】Ω
02-16 Rotor resistance of motor 1
Range
【
0.001~60.000】Ω
02-17 Leakage inductance of motor 1
Range
【
0.01~200.00】Mh
02-18 Mutual inductance of motor 1
Range
【0.1~6553.5】mH
02-19 No-Load Voltage of motor 1
Range
220V:【
50~240】V
440V:【100~480】V
Motor parameters settings are shown as below. When selecting motor 1 in the period of
motor parameters tuning, these motor parameters are automatically set (17-10 = 1). In
general, there is no need to do adjustment, except some special applications such as
fixed-horsepower control of axis motor of machine tool and so on.
For permanent magnet motor parameters settings, please refer to Group 22
(1) Setting of motor pole number (02-07)