Figure 4.3.18 9-speed time diagram
*1. When 00-05 = 1,multi-speed frequency reference is input through terminal AI1 or AI2
(8). Forward jog run command (FJOG) (setting=06).
(9). Reverse jog run command (RJOG) (setting =07).
Jog orientation can be set to forward or reversal.
setting=06: FJOG command (ON: Set jog frequency to forward by 00-18)
=07: RJOG command (ON: Set jog frequency to reverse by 00-18).
.The priority of FJOG and RJOG commands is higher than that of other frequency
command.
.If FJOG and RJOG commands are started more than 500 ms, set the stop way by
07-09(Stop way selection)to stop operation.
(10). UP frequency increasing command (setting = 08).
(11). Down frequency decreasing command (setting = 09).
. You can use digital operator (see Parameter11-56) or external multi-function
digital input (terminals S1 to S8) to increase or decrease the output frequency of
the inverter when the motor is operating.
. When using an external multi-function digital input terminals to perform UP /
DOWN operation, set 00-05(Source selection of main frequency command)to
2(Terminal UP /DOWN) and then set any one parameter from 03-00 to 03-07 to
08(UP command) and 09 (DOWN command). You need to use two terminals to