4-121
(2) Periodic operation (06-00 = 2, 5)
Inverter will periodically repeat the same cycle.
06-00 = 2
06-01~06-47 the setting is the same as that of Example 1 .
Figure 84.3.53 Periodic automatic operation
(3) Single cycle automatic operation mode (06-00 = 3, 6)
The inverter will finally keep on operating at the speed of final step.
06-00 = 3
06-32~06-35 = 1 (Forward)
06-36~06-47 = 0
Other parameter settings are the same as that of Example 1.
Figure 4.3.54 Single cycle automatic operation (continuous)
06-00 = 1 to 3: If the inverter is restarted after stop, it will start from the incomplete step
for further operation based on the setting of 06-00.
06-00 = 4 to 6: If the inverter is restarted after stop, it will start from a new cycle for
further operation based on the setting of 06-00.
· Acceleration/deceleration time is set by 00-14 and 00-15 of automatic operation mode.
· If the settings from 06-16 to 06-31 are 0, the automatic operation mode will not be enabled.
Output