4-208
22- IPM Motor Parameter Group
22- 00
PM motor rated power
Range
【
0.00~600.00】Kw
22- 01
PM motor rated voltage
Range
【50~240】V:220V
【100~480】V:440V
22- 02
PM motor rated current
Range
25%~200% inverter’s rated current
22- 03
PM motor’s pole numver
Range
【2~96】Poles
22- 04
PM Motor’s rated rotation speed
Range
【0~60000】rpm
22- 05
PM motor’s maximum rotation speed
Range
【0~60000】rpm
22- 06
PM motor rated frequency
Range
【0.0~400.0】Hz
PM motor’s parameter setting is shown as below. This parameter group can restore the
default value by the set parameter (13-08). Before initialization, please firstly confirm the
models of parameter (13-00) and ensure there is not mistake.
(01) PM motor rated power (22-00)
Set the power value on the motor nameplate.
(02) PM motor rated voltage (22-01)
Set the voltage of full load on the motor nameplate.
(03) PM motor rated current (22-02)
Set the current of full load on the motor nameplate.
(04) PM motor pole numver (22-03).
Set the motor pole number to the one on motor nameplate.
(05) PM motor rated speed (22-04)
It is need to set one of 22-04 or 22-06 only, the program will automatically calculate
the other one. The calculation formula is shown as below:
n (22-04) = 120*f(22-06) / P(22-03)
(06) PM motor maximum rotation speed (22-05)
Set the motor rotation speed on the nameplate.
(07) PM motor rated frequency (22-06)
Set the motor frequency on the nameplate.
22- 16
Offset angle of the magnetic pole and PG origin
Range
【0~360】deg
22- 17
PM motor tuning
Range
【0】: None
【1】: Magnetic pole alignment and loop adjustment
【2】: Magnetic pole alignment
22- 18
Fault history of PM motor tuning