6-3
6.2 AC reactor
‧When the capacity of power system is much larger than the inverter capacity or the
inverter is very close to the power system wiring (in 10 meters), or the factor of the
power supply needs to be increased, an external AC reactor may be added in.
‧
Please select an AC reactor according to the following table.
Table 6.2 List of
Model AC reactor
V HP
Rated Current(A)
HD/ND
Part Number Specification(mH/A)
1
5/6
3M200D1610021 2.1mH/5A
2
8/9.6
3M200D1610030 1.1mH/10A
220V
1ψ/3ψ
3
11/12
3M200D1610048 0.71mH/15A
5.4
17.5/21
3M200D1610056 0.53mH/20A
7.5
25/30
3M200D1610064 0.35mH/30A
10
33/40
3M200D1610072 0.265mH/40A
15
47/56
3M200D1610081 0.18mH/60A
20
60/69
3M200D1610099 0.13mH/80A
25
73/79
3M200D1610102 0.12mH/90A
30
85/110
3M200D1610111 0.09mH/120A
40
115/138
3M200D1610269 0.07mH/160A
50
145/169
3M200D1610277 0.05mH/200A
60
180/200
3M200D1610285 0.044mH/240A
75
215/250
3M200D1610293 0.038mH/280A
100
283/312
3M200D1610307 0.026mH/360A
125
346/360
220V
3ψ
150
415/450
1
3.4/4.1
3M200D1610137 8.4mH/3A
2
4.2/5.4
3M200D1610145 4.2mH/5A
3
5.5/6.9
3M200D1610153 3.6mH/7.5A
5.4
9.2/11.1
3M200D1610161 2.2mH/10A
7.5
14.8/17.5
3M200D1610170 1.42mH/15A
10
18/23
3M200D1610188 1.06mH/20A
15
24/31
3M200D1610196 0.7mH/30A
20
31/38
3M200D1610200 0.53mH/40A
25
39/44
3M200D1610218 0.42mH/50A
30
45/58
3M200D1610226 0.36mH/60A
40
60/72
3M200D1610234 0.26mH/80A
50
75/88
3M200D1610242 0.24mH/90A
60
91/103
3M200D1610251 0.18mH/120A
75
118/145
3M200D1610315 0.15mH/150A
100
150/165
3M200D1610323 0.11mH/200A
125
180/208
3M200D1610331 0.09mH/250A
150
216/250
3M200D1610340 0.06mH/330A
175
260/296
3M200D1610340 0.06mH/330A
215
295/328
4M200D0010008 0.05mH/400A
250
370/414
300
450/515
440V
3ψ
375
523/600
(Note) AC reactors listed in this table are only applicable to the converter input side.
Please don’t connect to the output side.
Both 220V class 50HP ~ 100HP and 440V class 75HP ~ 215HP have built in DC
reactors. If it is necessary in application, AC reactor can be added in.