4-31
Group 10 PID Function Group
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
Attrib
ute
10-10
PID Primary Delay
Time
0.00~10.00 0.00 s O O O O O O *1
0: Invalid
1: Warning
10-11
PID Feedback Loss
Detection Selection
2: Fault
0 - O O O O O O
10-12
PID Feedback Loss
Detection Level
0~100 0 % O O O O O O
10-13
PID Feedback Loss
Detection Time
0.0~10.0 1.0 s O O O O O O
10-14 PID integral limit 0.0~100.0 100.0 % O O O O O O *1
10-15 Retain
10-16 Retain
10-17
Start frequency of PID
sleep
0.00~180.00 0.00 Hz O O O O O O
10-18
Delay time of PID
sleep
0.0~255.5 0.0 s O O O O O O
10-19
Frequency of PID
waking up
0.00~180.00 0.00 Hz O O O O O O
10-20
Delay time of PID
waking up
0.0~255.5 0.0 s O O O O O O
10-21 Retain
10-22 Retain
10-23 PID limit 0.00~100.0 100.0 % O O O O O O *1
10-24 PID output gain 0.0~25.0 1.0 - O O O O O O
0: No allowing reversal output
10-25
PID reversal output
selection
1: Allow reversal output
0 - O O O O O O
10-26
PID target
acceleration/deceleratio
n time
0.0~25.5 0.0 s O O O O O O
10-27
PID feedback dispay
bias
-99.99~99.99 0.00 - O O O O O O
10-28
PID feedback display
gain
0.00~99.99 1.00 - O O O O O O
0: invalid
1: valid
10-29 PID sleep selection
2: set by DI
1 - O O O O O O