44
Group 17: Automatic Tuning Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
17-00
Mode Selection
of Automatic
Tuning*
0: Rotation
Auto-tuning
VF:2
VF+PG
:2
SLV:6
SV:6
SLV2:6
1: Static Auto-
tuning
2: Stator
Resistance
Measurement
3: Reserved
4: Loop Tuning
5: Rotation
Auto-tuning
Combination
(item: 4+2+0)
6: Static Auto-
tuning
Combination
(item: 4+2+1)
17-01
Motor Rated
Output Power
0.00~600.00 KVA
17-02
Motor Rated
Current
0.1~1200.0 KVA
17-03
Motor Rated
Voltage
200V: 50.0~240.0
-
400V: 100.0~480.0
-
575V:150.0~670.0
-
690V: 180.0~804.0
-
17-04
Motor Rated
Frequency
4.8~599.0
50.0/
60.0
17-05
Motor Rated
Speed
0~24000 KVA
17-06
Pole Number of
Motor
2~16 (Even) 4
17-07
PG Pulse
Number
0~60000 1024
17-08
Motor no-load
Voltage
200V: 50~240
-
400V: 100~480
575V: 420~600
690V: 504~720
17-09
Motor
Excitation
Current
0.01~600.00 -
ï¿­1
17-10
Automatic
Tuning Start
0: Disable
0
1: Enable
17-11
Error History of
Automatic
Tuning
0: No error
0
1: Motor data
error
2: Stator
resistance
tuning error
3: Leakage
induction tuning
error
4: Rotor
resistance
tuning error
5: Mutual
induction tuning
error
Group 17: Automatic Tuning Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
6: Encoder
error
7: DT Error
8: Motor’s
acceleration
error
9: Warning
17-12
Proportion of
Motor Leakage
Inductance
0.1~15.0 3.4
17-13
Motor Slip
Frequency
0.10~20.00 1.00
17-14
Selection of
Rotation Auto-
tuning
0: VF Rotation
Auto-tuning
1: Vector
Rotation Auto-
tuning
0
KVA: The default value of this parameter will be
changed by different capacities of inverter.
*: The default value is 1 in VF/ VF+PG mode while
the default value is 0 in SLV/ SV/ SLV2 mode.
*: It is suggested that HD/ ND mode (00-27) and
application presets (00-32) be selected first
before motor performs auto-tuning.
Note: The value of mode selection of automatic
tuning is 6 (Static Auto-tuning Combination). When
do auto-tuning with no-load motor, it suggest select
17-00=5 (Rotation Auto-tuning Combination)
ï¿­1:
It can be set when 17-00=1, 2, 6.
Group 18: Slip Compensation Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
18-00
Slip
Compensation
Gain at Low
Speed.
0.00~2.50
VF:0.00
*1
SLV*
18-01
Slip
Compensation
Gain at High
Speed.
-1.00~1.00 0.0 *1
18-02
Slip
Compensation
Limit
0~250 200
18-03
Slip
Compensation
Filter Time
0.0~10.0 1.0
18-04 Regenerative 0: Disable 0

Other manuals for TECO A510s Series