4-34
Group 08 Protection Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
08-48 Selection of Fire Mode
0:Disable
1:Enable
0 O O O
08-49
Multi-Function Input
Terminal Status of Fire
Mode
0:Reset after Power Off
1:Reset after Terminal Removed
0 O O O
08-50
Multi-Function Terminal
Status of Fire Mode
xxx0b:S6 A Contact
xxx1b:S6 B Contact
0000b - O O O
08-51
Motor Speed Setting
Source of Fire Mode
0:Fire Mode Speed(08-52)
1:PID Control
2:AI2
0 - O O O
08-52
Motor Speed of Fire
Mode
0.00~100.00 100.00 % O O O
08-53
PID Detection Level of
Fire Mode
0~100 0 % O O O
08-54
Delay Time of Fire
Mode PID Loss
0.0~10.0 0.0 s O O O
08-55
PID Feedback Loss
Detection Selection of
Fire Mode
0:Keep Running
1:Fire Mode Speed(08-52)
2:Max. Output Frequency of Motor 1 (01-02)
0 - O O O
08-56
Detection Level of Fire
Mode AI2 Signal
0~100 0 % O O O
08-57
Delay Time of Fire
Mode AI2 Signal Loss
0.0~10.0 0.0 s O O O
08-58
Selection of Fire Mode
AI2 Signal Loss
0:Keep Running
1:Fire Mode Speed(08-52)
2:Maximun Output Frequency (01-02)
0 - O O O
08-59
Fire Mode Motor
Direction
0:Forward
1:Reverse
0 - O O O
08-60 Fire Mode Password 00000~65534 0 - O O O
***STO function only be designed in EMC filter built-in models.