4-35
Group 09 Communication Parametes
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
09-00
INV Communication
Station Address
1~32 1 - O O O *3
09-01
Communication
Mode Selection
0:MODBUS
1:BACnet
3:PUMP in Parallel Connection
0 O O O *3
09-02
Baud Rate Setting
(bps)
2:4800
3:9600
4:19200
5:38400
4 - O O O *3
09-03 Stop Bit Selection
0:1 Stop Bit
1:2 Stop Bit
0 - O O O
*3
09-04 Parity Selection
0:No Parity
1:Even Bit
2:Odd Bit
0 - O O O
*3
09-05
Communication
Data Bit Selection
0:8 Bit Data
1:7 Bit Data
0 - O O O
*3
09-06
Communication
Error Detection Time
0.0~25.5 0.0 s O O O
*3
09-07 Fault Stop Selection
0:Deceleration to Stop By Deceleration Time 1
1:Coast to Stop
2:Deceleration to Stop By Deceleration Time 2
3:Keep Operating
3 - O O O
*3
09-08
Comm. Fault
Tolerance Count
1~20 1 - O O O *3
09-09 Waiting Time 5~65 5 ms O O O *3
09-10
BACNET Device
Instance Number
1~254 1 O O O
*3:Parameter group 09 will not be effected by factory setting. (13-08).