4-96
01- 02 Base frequency of motor 1
Range 【4.8~599.0】Hz
01- 03 Maximum output voltage of motor 1
Range
200V:【0.1~255.0】V
400V:【0.2~510.0】V
01- 04 Middle output frequency 2 of motor 1
Range 【0.0~599.0】Hz
01- 05 Middle output voltage 2 of motor 1
Range
200V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 06 Middle output frequency 1 of motor 1
Range 【0.0~599.0】Hz
01- 07 Middle output voltage 1 of motor 1
Range
200V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 08 Minimum output frequency of motor 1
Range 【0.0~599.0】Hz
01- 09 Minimum output voltage of the motor 1
Range
200V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 12 Base frequency of motor 1
Range 【4.8~599.0】Hz
01- 13 Base output voltage of motor 1
Range
200V:【0.0~255.0】V
400V:【0.0~510.0】V
V/F curve setting (01-02~01-09 and 01-12~01-13)
Select any of the predefined V/F curves setting 0 to E that best matches your application and
the load characteristic of your motor, choose a custom curve setting F or FF to set a custom
curve.
When setting the frequency related parameters for a custom V/F curve values make sure as
follows, the SE03 V/F curve tuning error is displayed when the frequency values are set
incorrectly.
F
max
> F
base
> F
mid2
> F
mid1
>F
min
(01-02) (01-12) (01-04) (01-06) (01-08)
When 01-04 and 01-05 (or 01-18 and 01-19) are set to 0, the inverter ignores the set
values of Fmin2 and Vmin2
The voltage values for 01-02~01-09 are irrelevant.
The value for maximum output voltage of motor 1(01-03) and the value for base output voltage
of motor 1(01-13) will depend on restore factory setting(13-08) to set the value of voltage.
When the control mode is changed parameter 00-00, 01-08 (F
min
) and 01-09 (V
min
) will
automatically be changed to the default setting of the selected control mode.
Custom V/F Curve Setting.