4-99
01-15 Torque compensation time
Range 【0~10000】ms
Set the torque compensation delay time in milliseconds.
Only adjust in the following situations:
①. Increase the value when experiencing motor vibration.
②. Decrease the value when motor torque response is too slow.
01- 16 Maximum output frequency of motor 2
Range 【4.8~599.0】Hz
01- 17 Maximum output voltage of motor 2
Range
200V:【0.1~255.0】V
400V:【0.2~510.0】V
01- 18 Middle output frequency 2 of motor 2
Range 【0.0~599.0】Hz
01- 19 Middle output voltage 2 of motor 2
Range
200V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 20 Middle output frequency 1 of motor 2
Range 【0.0~599.0】Hz
01- 21 Middle output voltage 1 of motor 2
Range
200V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 22 Minimum output frequency of motor 2
Range 【0.0~599.0】Hz
01-23 Minimum output voltage of motor 2
Range
200V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 24 Base frequency of motor 2
Range 【4.8~599.0】Hz
01- 25 Base voltage of motor 2
Range
200V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 26 V/F Curve Selection of Motor 2
Range 【0~FF】
Note 1:Motor 2 V/F curve uses the same settings as motor 1.
Note 2:Motor 2 V/F curve is the same as Motor 1, please refer to Table 4.4.3~26P
Note 3:Parameter 01-16~01-25 will be changed when the value of 01-26 is changed.