4-109
Figure 4.3.28 Multi-speed operation selection
Speed
Multi-function digital input (S1 to S6)
*4
Frequency selection
Jog
frequency
reference
Multi-speed
frequency 3
Multi-speed
frequency 2
Multi-speed
frequency 1
Multi-speed
frequency 0
1 0 0 0 0 0
Frequency command 0( 05-01) or
main speed frequency
*2
2 0 0 0 0 1 frequency reference 1 ( 05-02) *3
3 0 0 0 1 0 Frequency command 2 ( 05-03)
4 0 0 0 1 1 Frequency command 3 ( 05-04)
5 0 0 1 0 0 Frequency command 4 ( 05-05)
6 0 0 1 0 1 Frequency command 5 ( 05-06)
7 0 0 1 1 0 Frequency command 6 ( 05-07)
8 0 0 1 1 1 Frequency command 7 ( 05-08)
9 0 1 0 0 0 Frequency command 8 ( 05-09)
10 0 1 0 0 1 Frequency command 9 ( 05-10)
11 0 1 0 1 0 Frequency command 10( 05-11)
12 0 1 0 1 1 Frequency command 11 ( 05-12)
13 0 1 1 0 0 Frequency command 12 ( 05-13)
14 0 1 1 0 1 Frequency command 13( 05-14)
15 0 1 1 1 0 Frequency command 14 ( 05-15)
16 0 1 1 1 1 Frequency command 15 ( 05-16)
17 1
*1
─ ─ ─ ─ Jog frequency command (00-18)
“0”:OFF, “1”:ON, “-“:Ignore
*1: Jog frequency terminal has a higher priority than multi-speed reference 1 to 4.
*2: When parameter 00-05=0 (frequency reference input = digital operator), multi-speed
frequency 1 will be set by 05-01 frequency reference setting1). When parameter 00-05=1
(frequency reference input=control circuit terminal), multi-speed frequency command 1 is
input through analog command terminal AI1 or AI2).
*3: Multi-speed operation is disabled when PID is enabled.
Wiring Example:
Figure 4.3.17 and 4.3.18 is the example of a 9 speed operation selection
Figure 4.3.17 Control Terminal Wiring Example