4-198
13- 08 Restore factory setting / Initialize
Range
【1】:2 wires initialization (50Hz) (220V/380V)
【2】:2 wires initialization (60Hz) (220V/380V)
【3】:2 wires initialization (50Hz) (230V/400V)
【4】:2 wires initialization (60Hz) (220V/460V)
【5】:2 wires initialization (50Hz) (220V/415V)
【6】:2 wires initialization (60Hz) (230V/400V)
【7】:2 wires initialization (50Hz) (220V/440V)
【8】:2 wires initialization (60Hz) (220V/440V)
【9】:2 wires initialization (60Hz) (220V/380V)
【10】:2 wires initialization (60Hz) (220V/380V)
【1112】:PLC initialization (RESET)
Use parameter 13-08 to initialize the inverter to factory default. It is recommended to write down
the modified parameters before initializing the inverter. After initialization, the value of 13-08 will
return to zero automatically.
13-08=1:2 wires initialization (220V/380V)
(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 380V (440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=2:2 wires initialization (220V/380V)
(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 380V (440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=3:2 wires initialization (230V/400V)
(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 400V (440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=4:2 wires initialization (230V/460V)
(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 460V (440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=5:2 wires initialization (220V /415V)
(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 415V (440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.