13-08=6:2 wires initialization (230V/400V)
(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 230V (220V calss) or 400V (440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=7:2 wires initialization (220V/440V)
(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 440V(440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=8:2 wires initialization (220V/440V)
(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 440V(440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=9:2 wires initialization (220V/380V)
(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 380V(440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=10:2 wires initialization (220V/380V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2) Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 380V(440V calss).
(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=1112:PLC initialization
Clear built-in PLC ladder logic and related values.
The following parameters will not be influenced by restore factory setting (13-08)
No. Parameters
00-00 Control Mode Selection
00-34 Language selection
00-27 HD/ND Mode Selection
01-00 V/F Curve Selection
01-26 V/F Curve Selection of Motor 2
13-00 Inverter Capacity Selection
13-03 Cumulative Operation Hours 1
13-04 Cumulative Operation Hours 2
13-05 Selection of Cumulative Operation Time