16- 07 Copy Function Selection
Range
【0】:Do not copy parameter
【1】:Read inverter parameters and save to the keypad
【2】:Write the keypad parameters to inverter
【3】:Compare parameters of inverter and keypad
16- 08 Selection of allowing reading
Range
【0】:Do not allow to read inverter parameters and save to the keypad
【1】:Allow to read inverter parameters and save to the keypad
LCD digital operator can be used to store and retrieve parameters
(1) Read:Save inverter parameters to the digital operator (INV → OP).
(2) Write:Write the parameters from the digital operator to the inverter (OP → INV)
(3) Verify:Compare the inverter parameters with the parameters in the digital operator.
16-07= 0:No action
(1) 16-07= 1:Read (all parameters are copied from the inverter to the keypad)
(2) 16-07= 2:Write (all parameter are copied from the keypad to the inverter)
(3) 16-07= 3:Verify (Compare the set value to the parameter of the digital operator)
Set 16-08=0
In order to prevent the saved parameter data stored in the digital operator fromaccidentally being
overwritten. When parameter 16-08=0 and the read operation is executed (16-07=1) a warning
message of "RDP Read Prohibited" will be displayed on the keypad and the read operation is
cancelled.
For the write-in operation requires the following items to match.
(1) Inverter type
(2) Inverter rated capacity and voltage