4-208
WRITE:Copy Keypad parameters to the Inverter
Steps LCD Display (English) Description
1
Select the copy function group (16) from the group menu.
2
Press the Read / Enter key and select parameter
(16-07) copy sel.
3
Press the Read / Enter key to display the data setting / read
screen (LCD display is inversed).
4
Change the set value to 2 (write) by using the up
arrow key.
5
(1) Use Read / Enter key to enable the read
operation, the display is shown as the left.
(2) The bottom of LCD display will show a bar to
indicate the read progress.
6
-ADV-
WRITE
COMPLETE
“WRITE COMPLETE” will be displayed on the keypad when
writing was successful. Inverter will show “WRITE Syslnit”
after 3 seconds, please re-power again, inverter will start to
download the parameters.
The error message of “WRE Write Error”may
occur on the keypad when writing parameters to
the inverter is prohibited.
If the error is displayed, press any key to remove
the error message and go back to parameter
16-07.
7
When DSP/FUN key is pressed, the display returns to
parameter 16-07.