4-210
Group 17 Automatic Tuning Parameters
17- 00 Mode selection of automatic tuning
Range
【0】:Rotational auto-tuning
【1】:Static auto-tuning
【2】:Stator resistance measurement
【3】:Reserved
【4】:Loop tuning
【5】:Rotational Auto-tuning Combination (Item: 4+2+0)
【6】:Static Auto-tuning Combination (Item: 4+2+1)
17- 01 Motor rated output power
Range 【0.00~600.00】kW
17- 02 Motor rated current
Range
VF mode:10%~120% of the inverter rated current
SLV mode:25%~120% of the inverter rated current
17- 03 Motor rated voltage
Range
200V:【50.0~240.0】V
400V:【100.0~480.0】V
17- 04 Motor rated frequency
Range 【4.8~599.00】 Hz
17- 05 Motor rated speed
Range 【0~24000】RPM
17- 06 Pole number of motor
Range 【2~16】pole
17- 08 Motor no-load voltage
Range
200V:【50~240】V
400V:【100~480】V
17- 09 Motor excitation current
Range 【15~70】% of motor rated current
17- 10 Automatic tuning start
Range
【0】:Disable
【1】:Enable
17- 12 Proportion of Motor Leakage Inductance
Range 【0.1~15.0】%
17- 13 Motor Slip Frequency
Range 【0.10~20.00】Hz
17- 14 Rotational Auto-tuning
Range
0】:VF type rotational auto-tuning
1】:Vector type rotational auto-tuning
(1) Values are for 200V class, double the values for 400V class
(2) In HD mode (00-27=0) the range is 0.0 to 400.0 Hz, 0.0 to 120.0Hz in for ND mode (00-27=1)
and 0.0 to 599.0Hz is high frequency mode.
(3) Based on the motor nameplate set the motor rated output power (17-01), motor output rated
current (17-02), motor rated voltage (17-03), motor rated frequency (17-04), motor rated speed
(17-05) and number of motor poles (17-06) to perform an auto-tune.