03-1X=32: Communication control contacts
Output is active when communication control is active.
03-1X=37: Detection Output of PID Feedback Loss
When PID feedback loss occurs (refer to parameters setting 10-11~10-13), this function will be ON.
03-1X=38: Brake Release
When this function is ON, Break release is enabled. Refer to parameters descriptions of 03-41~03-42.
03-1X=42: Over-High Pressure
Refer to the setting of parameters 23-12~23-14 for the warning / fault.
03-1X=43: Over-Low Pressure
Refer to the setting of parameters 23-15~23-17 for the warning / fault.
03-1X=44: Loss of Pressure Detection
Refer to the setting of parameters 23-18~23-19 for the warning / fault.
03-1X=45: PID Sleep
PID sleep will be informed.
03-1X=46: Over-High Flow
Refer to the setting of parameters 23-48~23-50 for the warning / fault.
03-1X=47: Over-Low Flow
Refer to the setting of parameters 23-51~23-53 for the warning / fault.
03-1X=48: Shortage of Low Suction
Refer to the setting of parameters 23-54~23-58 for the warning / fault.
03-1X=49: RS-485 communication error
When RS-485 communication error, the output terminal is closed, please refer to the description of
09-06~09-07.
03-1X=54: Turn on short-circuit braking
Output terminal is closed when Turning on short-circuit braking
03-1X=57: Low Current Detection
When output current ≦ 03-48, the relay is active.
03-1X=58: Frequency Deceleration Detection
When output frequency < frequency command- 03-14 in deceleration, the relay is active.
03-1X=59: Over Temperature Detection
The Heat Sink Temperature > 08-46, the relay is active, the Magnetic Hysteresis Zone is set by 08-47.
03-13 Frequency Detection Level
Range
【0.0~599.0】 Hz
03-14 Frequency Detection Width
Range
【0.1~25.5】 Hz
03-44 Frequency Detection Level 2