4-123
Function Detection operation of frequency confirmation Description
Output
frequency
detection 5
Output frequency detection 5
signal is ON in acceleration when
the output frequency rises above
the frequency detection level 3
(03-46) + frequency detection
width 3 (03-47).
Output frequency detection 5
signal is OFF in deceleration
when the output frequency
declines to the frequency
detection level 6 (03-52).
Any of the digital outputs function
(03-11, 03-12 or 03-39) can be
set to 52 (Output frequency
detection 5).
Output
frequency
detection 6
Output frequency detection 6
signal is OFF in acceleration
when the output frequency rises
above the frequency detection
level 3 (03-46) + frequency
detection width 3 (03-47).
Output frequency detection 6
signal is ON in deceleration when
the output frequency declines to
the frequency detection level 6
(03-52).
Any of the digital outputs function
(03-11, 03-12 or 03-39) can be
set to 53 (Output frequency
detection 6).