4-129
03- 37
Timer ON Delay (DI/DO)
Range
【
0.0~6000.0】Sec
03-38
Timer OFF Delay (DI/DO)
Range
【
0.0~6000.0】Sec
Enable the timer function be setting one of multi-function input parameters 03-00~03-05 (S1 to S6) to 35
(timer function input) and one of multi-function output parameters 03-11, 03-12, 03-39 (R1A-R1C to R3A-
R3C) to 27 (timer function output).
The timer function can be used to implement a timer relay. Use timing parameter 03-37 and 03-38 to set
the timer ON / OFF delay.
Timer output is turned ON when the multi-function timer input is ON for the time specified in parameter
03-37.
Timer output is turned OFF after the multi-function timer input is OFF for the time specified in parameter
03-38.
Timing example:
ON
ON
ON
ON
Timer input function
03-37
03-38
03-37
03-38
Timer output function
03- 40 Up/down Frequency Width Setting *1
Range
【0.00~5.00】Hz
*1: It is new added in inverter software V1.4.
For example: Set terminal S1: 03- 00=【8】(Up Frequency Increasing Command), S2:03- 01=【9】(DOWN
Frequency Decreasing Command) and 03- 40=【△】Hz.
Mode1: When 03-40 is set to 0Hz, it will maintain the original up/down function, shown as Fig. 4.4.20.
Mode2: When 03-40 is not set to 0Hz and terminal conduction time is lower than 2 sec, conducting one
time leading to frequency variation △Hz (setting frequency by 03-40)。