4-131
03- 41 Torque Detection Level *1
Range
【0~150】%
03-42
Delay Time of Braking Action *1
Range
【0.00~65.00】Sec
*1: It is new added in inverter software V1.4.
Function of Brake Release:
It requires function of frquecny agree to use, shown as the following figure.
When output frequency is larger than frequency detection level (03-13) and output torque is larger than
torque detection level (03-41) during Inverter operation, it will delay braking action delay time (03-42) and
then release brake.
It is also recommended to be with the use of start and stop frequency locked function (11-43~11-46),
shown as the following figure:
03-43
UP/DOWN Acceleration/ Deceleration Selection
Range
【0】: Acceleration/Deceleration Time 1
【1】: Acceleration/Deceleration Time 2
Calculate the acceleration/ deceleration time of frequency command by switch the function of UP/DOWN
from parameter 03-43. Ex: H1 (set frequency increment at acceleration) and H2 (set frequency
increment at deceleration).