Chapter 4 Software index
4-8
46
Multi-function output
T+,T- (option)
000: Run
001: Frequency reached
(Set frequency ± F23)
002: Frequency is within the range
set by (F22±F23)
003: Frequency detection (>F22)
004: Frequency detection (<F22)
005: Fault terminal
006: Auto-restart
007: Momentary power loss
008: Emergency Stop(E.S.)
009: Base Block(b.b.)
010: Motor overload protection
011: Inverter overload protection
012: retain
013: Power ON
014: Communication error
015: Output current detection(>F26)
005
47
Remote keypad control
selection
000: Disable (no signal loss detection)
001: Enable. On signal loss stop
according to F09
002: Enable. Runs at the last set
frequency. On signal loss
Stop is according to F04 setting or
Stop key on keypad.
000
Stop inverter
then connect
remote
keypad for
proper
operation *4
48 Copy module
000: Copy module disable
001: copy to module from inverter
002: copy to inverter from module
003: read/ write check
000 *3
49
Inverter communication
address
001 ~ 254 001 *3 *4
50 Baud rate (bps)
000: 4800
001: 9600
002: 9200
003: 38400
003 *3 *4
51 Stop bit
000: 1 Stop bit
001: 2 Stop bit
000 *3 *4
52 Parity bit
000: No parity
001: Even parity
002: Odd parity
000 *3 *4
53 Data bits
000: 8 bits data
001: 7 bits data
000 *3 *4
54
Communication error
detection time
00.0 ~ 25.5 Sec 00.0 *3*5
55
Communication error
operation selection
000: Deceleration to stop.
(F02: Deceleration time 1).
001: Coast to stop.
002: Deceleration to stop.
(C12: Deceleration time 2).
003: continue operating.
000 *3*5