Chapter 4 Software index
4-12
Note: C00=001, reverse command is disabled.
F07 Frequency upper limit (Hz): 01.0 - 200
F08 Frequency lower limit (Hz): 00.0 - 200
Note: If F07 = 0 Hz and frequency command = 0 Hz, the inverter will 0-speed stop.
If F08 > 0 Hz and frequency command F08, inverter will run at F08 set value.
F09 Stopping method 000: Decelerate to stop
001: Free run ( Coast) to stop
1.) F09 = 000: after receiving stop command, the motor will decelerate to stop according to
setting of F02, deceleration time 1.
2.) F09 = 001: after receiving stop command, the motor will free-run (Coast) to stop.
F10 Status monitoring
display
000: Disable
001: Enable.
F10 = 001 displays motor current, voltage, DC bus voltage, and PID feedback.
Out put frequency
F07 (Frequency upper limit)
F08 (Frequency lower limit)
(Note)
Commanded Frequency
Terminal
Terminal
Terminal
Figure 4-4 Control Method Sequences
Figure 4-5 Frequency Limits