Chapter 4 Software index
4-17
F19 AIN Bias: 000: Positive 001: Negative
F20 AIN signal slope direction. 000: Positive 001: Negative
C45 AIN signal scan time confirmation. (mSec × 8): 001 – 100
Refer to F17/F18 description
The inverter reads A/D average value every C45 x 8mS. The user can set scan interval time according
to noise levels in the operation environment. Extend C45 if noise is a problem, however the response
speed will be slower.
F21 Multi function output RY1
000: Run
001: Frequency reached (Preset target frequency ± F23)
002: Frequency reached (Preset output frequency level (F22) ±F23)
003: Frequency Detection (>F22)
004: Frequency Detection (<F22)
005: Fault output
006: Auto restart
007: Momentary power loss
008: Emergency Stop(E.S.)
009: Base Block(b.b.)
010: Motor overload protection
011: Inverter overload protection
012: retain
013: Power On
014: Communication error
015: Output current detection
F22 Preset Output frequency reached =00.0 ~ 200Hz
F23 Frequency detection range =00.0 ~ 30Hz
Figure 4-8a Frequency Reached (F21/C46=1)