4-67
08- 07=2: Cooling fan runs continuously.
08- 07=3: Cooling fan is Disabled.
08- 08 AVR function
Range
0:AVR function enable
1:AVR function disable
2:AVR function disable for stop
3:AVR function disable for Deceleration
4:AVR function disabled for stop & Deceleration from one speed to another
speed.
5:when VDC>(360V/740V), AVR function is disabled for stop and
deceleration
Automatic voltage regulator function provides a level of output voltage stability when there is
input voltage instability. So when 08-08=0, Input voltage fluctuations will not effect the output
voltage.
08-08=1, Input voltage fluctuations will cause fluctuations on output voltage.
08-08=2, AVR is disabled during stopping to avoid an increase in stopping time.
08-08=3, AVR is disabled only during deceleration from one speed to another speed. This will
avoid longer than required deceleration time.
08-08=4, AVR function disabled for stop & Deceleration from one speed to another speed.
08-08=5, When VDC>360(200V series) or VDC>740V(400V series), AVR function is disabled
for stop and deceleration
08- 09 Input phase loss protection
Range
0:Disabled
1:Enabled
When 08-09=1:On phase loss warring message PF is displayed.
08- 10
PTC Motor Overheat Function
Range
0:
Disable
1:
Decelerate to stop
2:
Coast to stop
3: Continue running, when warning level is reached.
Coast to stop, when protection level is reached.
08- 11
PTC Signal Smoothing Time
Range
0.00 ~ 10.00Sec
08- 12
PTC Detection Time Delay
Range
1 ~ 300Sec
08- 13
PTC Protection Level
Range
0.1 ~ 10.0V
08- 14
PTC Detection Level Reset
Range
0.1 ~ 10.0V
08- 15
PTC Warning Level
Range
0.1 ~ 10.0V