4-69
08- 16
Fan Control Temperature Level
Range
【10.0~50.0】
°C
When 08-07=【0】 ( Heat sink temperature detection control for cooling fan). Fan will run when
temperature of heat sink is higher than 08-16; When temperature of heat sink decrease
below ”setting value of 08-16 minus 20
°C”, fan will stop.
08- 17 Over current protection level
Range 【0.0~60.0】 A
08- 18 Over current protection time
Range 【0.0~1500.0】 s
When the output current exceeds the setting value of 08-17 and then keep running exceeds
the setting value of 08-18, inverter will show “OL3” alarm and then stop running.
(When the output current lower than the setting value of 08-17, 08-18 will be reset, over
current protection function will be closed when 08-17 set to “0”.