4-77
10-17 PID Sleep Frequency Level
Range 0.00~599.00Hz
10-18 PID Sleep Function Delay Time
Range 0.0 ~25.5s
10-19 PID Wake up frequency Level
Range 0.00 ~ 599.00Hz
10-20 PID Wake up function Delay Time
Range 0.0 ~ 25.5s
When PID output frequency is less than the sleep threshold frequency and exceeds the
time of sleep delay, the inverter will decelerate to 0 and enters PID sleep mode.
When PID output frequency is larger than the Wake up threshold frequency inverter will
enter the PID mode again as shown in the timing diagram below.
10-21
Max PID Feedback Level.
Range
0 ~ 999
10-22
Min PID Feedback Level.
Range
0 ~ 999
Example: If 10-21=100 and 10-22=50 and the unit for the range from 0 to 999 will be
defined with the parameters setting of 12-02 , actual feedback value variation range, will be
scaled to 50 and 100 only for display, as Shown below.
10-21=100
10-22=50
Min 0%
0V/0mA(or 2V/4mA)
Max 100%
(10V/20mA)
999
PID fback