4-80
11- 08 Skip frequency 1
11- 09 Skip frequency 2
11-10 Skip frequency 3
Range
0.00 ~ 599.00Hz
11-11 Skip frequency range. (± frequency band)
Range
0.00 ~ 30.00Hz
Skip frequency parameters can be used to avoid mechanical resonance in certain applications.
Example: 11-08=10.00(Hz); 11-09=20.00(Hz); 11-10=30.00(Hz); 11-11=2.00(Hz).
±2Hz=8~12Hz
±2Hz=18~22Hz Skip frequency
±2Hz=28~32Hz
10Hz 20Hz 30Hz
11-13 Regeneration Prevention Function
Range
0: Regeneration prevention function is disabled
1: Regeneration prevention function is enabled
2: Regeneration prevention function is enabled only during constant
speed
Regeneration Prevention Function:
During excessive energy regeneration, the Vpn (DC bus) voltage will Increase and lead to
OV (over voltage), to avoid over voltage due to regeneration the output frequency will be
increased..
Regeneration prevention function can be set according to the selections above.
Example: Regeneration prevention during acceleration.
11-11
11-10
11-09
11-08