4-54
04-11 Analog Output (AO) function selection.
Range
【0】:Output frequency
【1】:Frequency Setting
【2】:Output voltage
【3】:DC Bus Voltage
【4】:Output current
Example: Set 04-11 required according to the following table.
0
10V
Xmax
A
Xmax( 04-11)
Xmax / 2
5 V
04-12 AO Gain
Range
【0 ~ 1000】%
04-13 AO Bias
Range
【0 ~ 100】%
04-14 AO Bias Selection
Range
【0】: Positive 【1】: Negative
04-15 AO Slope
Range
【0】: Positive 【1】: Negative
Select the Analog output type for the multifunction analog output on terminal (TM2) as
required by parameter 04-11. Output format is 0-10Vdc.The output voltage level can be
scaled and modified by parameters 04-12 to 04-15 If necessary.
The modification format will be same as the examples shown previously for Analog Voltage
Input (AVI) parameters 4-02 to 4-05.
Note: the max output voltage is 10V due to the hardware of the circuit.
Use external devices that require a maximum of 10V dc signal.
04-16 Potentiometer Gain on Keypad
Range
【0 ~ 1000】%
04-17 Potentiometer Bias on Keypad
Range
【0 ~ 100】%
04-18 Potentiometer Bias Selection on Keypad
Range
【0】: Positive 【1】: Negative
04-19 Potentiometer Slope on Keypad
Range
【0】: Positive 【1】: Negative
04-11 A Xmax
【0】
Output frequency upper frequency limit
【1】
Frequency Setting upper frequency limit
【2】
Output voltage Motor Rated Voltage
【3】
DC Bus Voltage
220V:0~400V
380V:0~800V
【4】
Output current 2 times rated current of inverter