Chapter 4 Software Index
4-22
2. The priority in reading frequency is Jog> preset speed>▲▼ on keypad or Up / Down or
communication control.
3. When 01-00 ~ 01-05 is set 17(Main/Alt Frequency Command Select), if the terminal is ON, the
inverter frequency command is set by parameter 00-05, if the terminal is Off, the inverter
frequency command is set by parameter 00-06.
00-07: Frequency Upper limit(Hz) 0.01 - 400.00
00-08: Frequency Lower limit(Hz) 0.01 - 400.00
※Note: When 00-08 = 0 Hz and frequency command is 0 Hz; the inverter will stop at 0 speed.
When 00-08 > 0 Hz and frequency command ≦00-08, the inverter will output the
00-08 preset value.
00-09: Acceleration time 1 (second) =0.1 – 3600.0
00-10: Deceleration time 1 (second) =0.1 – 3600.0
1. Formula for calculating acceleration and deceleration time: The denominator is base on the
rated frequency of motor.
0 or preset frequency
06 04
×
=
0- 09( 10- 05)
accel er at i on t i me
0
deceleration tim e
06 04
=
0- 10( or 10- 06) pr eset f r equency
2. When 01-00 ~ 01-05 is set 08 (the second acceleration and deceleration time),the first
acceleration/ deceleration or the second acceleration/ deceleration/ will be set by OFF or ON
the external input terminal.
3. When 01-00 ~ 01-05is set 06/07 (Jog),Jog run is controlled by external terminals. The
acceleration and deceleration action will be at Jog acceleration and deceleration time.
The list setting:
Internal frequency
00-07 (upper frequency limit)
00-08 (lower frequency
(Note)
Figure 4-6 Frequency reference limits