54
Note:
1. Accel & Decel S-Curves ( 1 or 2 ) can be selected by using the multifunctional input
terminals along with the programming of (Fn_56) (Fn_57) or (Fn_58 to (4).
2. The S-Curve function is disabled when (Fn_80) (Fn_81) is set to (0).
3. The S-Curve ramp pattern will reflect the ramp pattern above if the S-Curve time in
(Fn_80) (Fn_81) is greater than (0).
4. Total Actual Accel and Decel times are calculated by adding the actual Accel and Decel
with the S-Curve time.
Fn_82: Energy Savings:
xx00: Energy saving disable
xx01: Energy saving controlled by multi-input terminals using pre-set speed functions
Fn_83: Energy saving gain: 0 - 100 %
100
12.5
0
50 100
Percenl Torquc and Horsepower
Percent Speed
Tor
q
ue
Horsepower
1. This function can be applied to Fans or Pumps that have loads with high starting inertia. In
these types of applications where the load is heavy during start-up but tapers off to a variable
torque type load at some point in the ramp curve, using function (Fn_83) to adjust the suitable
gain (voltage level) at the target speed will reduce the V/Hz ratio saving energy.
2. The Energy saving function is available only if (Fn_56) (Fn_57) or (Fn_58) (multi-function
input) are set to (08) or (24).
3. When (Fn_82) is set to (xx01) and (Fn_56) (Fn_57) or (Fn_58) are set to (08) When the
multi-function input terminal is turned ON, the output voltage will decrease gradually to the
previous output voltage x (Fn_83). When the input terminal is turned off, the output voltage
will increase to the previous voltage gradually.
Activation of Energy