7
7.1 Wind sensor (only for “S” version)
The wind sensor (ANEM4, 4 pulses/rotation) detects if the wind speed exceed the threshold, set with DIP1-2
(pag.3). It has the highest priority among the sensors. If the alarm is active:
7.2 Rain sensor (only for “S” version)
When the sensor detects the rain and the alarm is activated, the device positions the slats of the pergola or moves
the motor of the awning to completely closed position. During the status of alarm L2 is ON and the control unit
does not execute any command. The alarm is off when the sensor doesn’t detect the presence of the rain for 20
seconds.
6. Conguration of working time (only for pergola application)
The conguration of the working time is necessary only for the application PERGOLA. The procedure below will
be applied just in case the DIP4 is set to OFF.
ON
1 2 3
Move DIP3 to ON. The buzzer makes a beep.
The functioning mode automatically switches to “HOLD-TO-RUN”.
P1
Move the awning to the upper limit (application closed).
Press P1 to memorize the limit. Buzzer will make a beep.
Move the awning to the lower limit (application open).
P1
Press P1 to memorize the limit. Buzzer will make a long beep and exits the procedure.
The functioning mode switch back to “AUTOMATIC”.
ON
1 2 3
Move DIP3 to OFF.
DIP4 APPLICATION WIND SPEED (Km/h)
ON Awning The control unit completely closes the awning (MOTOR UP command)
OFF Pergola The control unit moves the slats to complete opening, then at 50% and it stops.
L1 ashes and the control unit does not execute any command.
The system resumes its normal operation 30 seconds after the alarm is OFF (speed lower than the threshold).