Manual NOVOS und thanos EVO
Seite 32 Thermokon Sensortechnik GmbH
Number of selectable fan stages
0 = 0
1 = 1
2 = 2
3 = 3
4 = 4
5 = 5
● ● 0 5 3
r / w
1309
0 = no
1 = yes
● ● ● 0 1 1
uint16
_t
1310
Minimum selectable Fan stage
0 = 0
1 = 1
2 = 2
3 = 3
4 = 4
5 = 5
● ● ● 0 5 0
r / w
uint16
_t
1311
Fan Stage after power reset
Preset Fan Stage after power reset
0 = OFF
1 = Stage 1
2 = Stage 2
3 = Stage 3
4 = Stage 4
5 = Stage 5
6 = Auto
● ● 0 6 6 r / w 1312
Value display on home screen
Select, which value should be displayed
in the home screen.
Bit 0: Display actual temperature
Bit 1: Display setpoint
Value = 0 -= OFF
● ● 0
3 r / w 1313