TI120 Series Variable Frequency Drive Detailed parameter introduction
- 133 -
P61.11
The number of pole pairs of
resolver
range:1~32
Factory default:1
P61.12
Sinusoidal signal offset
range:1~65535
Factory default:0
P61.13
Cosine signal offset
range:1~65535
Factory default:0
P61.14
Sinusoidal signal gain
range:1~8192
Factory default:4096
P61.15
Cosine signal gain
range:1~8192
Factory default:4096
P62 Motor characteristics parameter
P62.00
Stator resistance of
asynchronous motor
range:0.001Ω~65.000Ω
Factory default:
Model determination
P62.01
Rotor resistance of
asynchronous motor
range:0.001Ω~65.000Ω
Factory default:
Model determination
P62.02
Leakage inductance of
asynchronous motor
range:0.01mH~650.00mH
Factory default:
Model determination
P62.03
Mutual inductance of
asynchronous motor
range:0.01mH~650.00mH
Factory default:
Model determination
P62.04
No-load current of
asynchronous motor
range:0.1A~P63.02
Factory default:
Model determination
P62.05
Saturation coefficient of
asynchronous motor
range:0.00%~100.00%
Factory default:
Model determination
The above group of parameters is characteristic parameters of asynchronous motors, which are
automatically defaulted as Factory default according to the power. The characteristic parameters of the
actual motor can be automatically obtained by static or rotating identification of the motor, or can be
provided by the motor manufacturer.
P62.06
Stator resistance of
synchronous motor
range:0.001Ω~65.000Ω
Factory default:
Model determination
P62.07
D-axis inductance of
synchronous motor
range:0.01mH~650.00mH
Factory default:
Model determination
P62.08
Q-axis inductance of
synchronous motor
range:0.01mH~650.00mH
Factory default:
Model determination
P62.09
Counter electromotive force of
synchronous motor
range:0.1mV~2000.0mV
Factory default:
Model determination
The above group of parameters is characteristic parameters of synchronous motors, which are
automatically defaulted as Factory default according to the power. The characteristic parameters of the
actual motor can be automatically obtained by static or rotating identification of the motor, or can be
provided by the motor manufacturer.
P63Motor nameplate parameters

Table of Contents