TOPVERT L1 Series
E-
15
Bit 4
(b0xxxx)
0: Changed parameter will be store
1: Changed parameter not store
Pr0-12
Auto Accelerate/
Decelerate
0: Linear Acc, linear Dec.
0
1: Auto Acc, linear Dec.
2: Linear Acc, auto Dec.
3: Auto Acc, auto Dec.
4: Linear Acc,/Dec., auto to prevent stall.
Pr0-13
Accelerate/ Decelerate
time unit
0: 0.01 Second
0
1: 0.1 Second
2: 1 Second
Pr0-14
PWM Carrier frequency
upper bound
0=0.7kHz
10
118kHz
Pr0-15
PWM Carrier frequency
lower bound
0=0.7kHz
10
118kHz
Pr0-16
Automatic Voltage
Regulation (AVR)
0: Enable Automatic Voltage Regulation
0
1: Disable Automatic Voltage Regulation
2: Disable Automatic Voltage Regulation while in
cancel
Pr0-17
Automatic Energy-Saving
Operation (AESO)
and others
Bit 0
(bxxxx0)
0: Disable Automatic Energy-Saving
Operate
b00000
1: Enable Automatic Energy-Saving
Operate
Bit 1
(bxxx0x)
0: Allow output voltage over source
voltage
1: Maximum output voltage equals to
source voltage
Bit 2
(bxx0xx)
0: For constant torque load application.
1: For variable torque load application.
Bit 3
(bx0xxx)
0: Regen-torque no slip compensation
1: Regen-torque with slip compensation
Bit 4
(b0xxxx)
0: Low noise mode operation
1: Quiet mode operation
Pr0-18
Source of the frequency
command
0: From PU
0
1: From RS485 communication port
2: From external analog signal
3: From external Up/Down terminals
4: (Factory Reserved)
Pr0-19
Source of the operation
command
0: From RS485 communication port or PU
0
1: From external terminals or PU
2: From PU
3: From external terminals
Pr0-20
Stop/ Run/safety lockout
Bit 0
(bxxxx0)
0: Ramp to stop
b00000
1: Coast to stop
Bit 1
(bxxx0x)
0: Terminal command not run after reset
1: Terminal command restart after reset
Bit 2
(bxx0xx)
0: Line start Lockout is enabled
1: Line start Lockout is disabled
Bit 3
(bx0xxx)
0: FWD/REV go through zero point
1: FWD/REV go not through zero point
Bit 4
(b0xxxx)
0: Linear Accel/Decel at high speed
zone
1: S-curve Accel/Decel at high speed
zone
Pr0-21
Direction limit
0: Enable Forward/Reverse operation
0
1: Disable Reverse operation
2: Disabled Forward operation