Control Loop
2-Way Multi-Purpose Pilot
Troubleshooting
Inlet pressure is too low.
Check the inlet pressure.
Pilot's adjusting screw is
completely closed.
Check the screw position.
Rotate anti-clockwise. Continue until the valve begins to
open.
No water is coming out of
pilot port #0.
Dismantle and clean pilot ports. Replace pilot if the
problem not solved.
Blocked inline finger filter (2).
Disconnect the upstream
tube. No firm water stream.
Clean or replace the filter.
Debris on the sealing seat.
Valve is constantly
discharging a small amount
of water.
Dismantle, clean, and check that the parts are not
damaged.
Continuous water discharge.
Unstable pressure
upstream of the valve
Dismantle and clean. Replace the pilot if the problem
persists.