EasyManua.ls Logo

Toshiba 1000 Series - Normal Display and Control Panels

Toshiba 1000 Series
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
FAULT or is on during active UPS internal errors (red). FAULT is
accompanied by an audible alarm. Press any of the front panel
buttons to cancel the alarm.
Status of the UPS, measurements, and alarms are all indicated on the LCD screen.
Figure 3 Control panels 1000/1500/2000/3000VA
Figure 4 Control panel 2400VA Tower/6000VA Rack Unit
7.4 Normal Display
The UPS status is shown in the normal display mode. The UPS Meters display and the
Setting display may be accessed by pressing the Return button on Tower Unit and
FUNC button on the Rack Unit.
Tower Unit
ON ON-LINE ON-BATT BYPASS FAULT
FUNC ENTER ON/OFF
Rack Unit

Other manuals for Toshiba 1000 Series

Related product manuals