18
TOSHIBA
CAPACITY 2.4kVA (1.68kW) 3.6kVA (2.52kW) 6kVA (4.2kW) 8kVA(5.6kW)
General
Topology True On-line, Isolation transformer on input of isolated models
Certifications UL,CUL,FCC class A
Input Characteristics
Input voltage Single-phase 240/208Vac (4 wire input / L-L, N, G), +10% to -30%
(Requires 2-120Vac to Neutral phases, unit automatically senses 120 or
180 deg phase shift)
Input frequency 45 - 65Hz (autosensing)
Input capacity 2.4kVA 3.6kVA 6.0kVA 8.0kVA
Input power factor > 0.95 for all loads
Current THD < 5% (linear load), < 10% (non-linear load)
Battery Characteristics
Battery type Valve Regulated Lead Acid, Flame Retardant
Backup time, fully charged
@ 0.7 power factor, 77 F 7 minutes minimum
Recharge time 24hr. (full), 12hr.(90%) for internal batteries only
Output Characteristics
Output voltage Single-phase 240/208/120Vac (4 wire output / L-L, N, G)
(Output synchronizes to input voltage)
Output voltage regulation +/- 3%
Output frequency +/-0.5Hz/1Hz/1.5Hz (factory or authorized service center selectable only)
AUTO/MAN frequency Factory or authorized service center selectable only
Voltage THD < 3% for linear load; < 6% for non-linear load
Common-mode noise < 1Vrms
Rated load power factor 0.7 (0.6 - 1.0) lag
Efficiency (ac-dc-ac) > than 85% (without battery charger)
Voltage transient < +/-8% (Load of 0 to 100 %)
Rated output current (rms) 10A 15A 25A 33.3A
Max. peak output current 30A 45A 75A 100A
Inverter overload capacity 125%-30sec/150%-10sec
Bypass overload capacity 125%-10min./1000%-1 cycle
Crest factor 3.0
Environment
Operating temperature 0 ~ 40° C (15 ~ 25° C recommended)
Storage temperature -15 ~ 40° C
Installation area To be installed in a well ventilated area free of airborne dust, metal
particles or flammable gas, allow at least 4 inches on all sides
Operating humidity 30 ~ 90%(no condensation)
Altitude < 1000m above sea level (output derated when used above 1000m)
Acoustical noise 50 dB (A) maximum @ 1 meter from front panel
Operation Diagnostics
Battery check Performed on start up, by schedule, on-demand (user configurable)
Input OV protection Standard
Battery lifetime UPS calculates battery replacement time based upon battery ambient
temperature (LCD display, LED and beeps)
UPS lifetime LCD indication given when usable lifetime of UPS is reached
Internal temperature UPS gives indication of internal temperature, alarm when high temperature
Event data storage 64-Supply Mode, 32-Back up, 16-Faults
STANDARD AND ISOLATED MODELS
UPS Specifications