39
Starting the UPS
Turn the main circuit breaker (MCCB) on the back of the UPS (see page 44) to the "on" position
(the breaker should normally remain in the "on" position).
Check that the LED on the front panel (see page 25 and 26) lights 'green'.
All LED's on the front panel may light for a moment when the input breaker is turned "on". This is
normal. The UPS will now be supplying power in the bypass mode.
Manual Run/Stop Operation
Stopping the UPS
To stop the UPS, press the key approximately 1 second until the LED changes
from green to "off". The UPS is now in the bypass mode.
To completely stop the UPS, turn the input breaker at the back of the UPS to the "off" position.
CAUTION
Note: If the input breaker is turned off while UPS is in the
bypass state, the output power stops. Any load devices will
lose power. Ensure that all sensitive loads have been previously
shut down.
CAUTION
Note: When running the UPS for the first time or after the
power failure backup operation, charge the battery for at least
24 hours (input breaker "on") before operating the connecting
load. Using the UPS without charging the battery shortens
the battery backup operation time, which could result in the
destruction of data in case of a power failure.
Press to begin UPS operation (see page 29 for startup screens).
General
Safety
Inspections &
Precautions
Connections
Equipment
Equipment
Specifications
EquipmentDisplay
Screens
Manual
Run/Stop
Protection
System
Maintenance
& Options
Dimensions &
Weights
Index
Reference
Operations
Key Functions
Display &
Stop
Run

Other manuals for Toshiba 1600 Series

Related product manuals