This manual contains important instructions
for 2.4, 3.6, 6.0, and 8.0 kVA that should be
followed during the installation and maintenance of the UPS and its batteries.
Hardwire type UPS units are not equipped with an overcurrent-protection device, nor an output disconnect
for the ac output. Therefore, a circuit breaker should be provided by the user between the UPS output and
the load input. This device should be rated as follows:
2.4 kVA: 240 Vac, 15A
3.6 kVA: 240 Vac, 20A
6 kVA: 240 Vac, 30A
8 kVA: 240 Vac, 40A
The maximum ambient temperatures in which the UPS units should be operated are as follows:
2.4 kVA: 104° F (40° C).
3.6 kVA: 104° F (40° C).
6 kVA: 104° F (40° C).
8 kVA: 104° F (40° C).
The nominal battery voltages for these models are as follows:
2.4 kVA: 144Vdc
3.6 kVA: 144Vdc
6 kVA: 216Vdc
8 kVA: 144Vdc
Servicing of the batteries should only be performed by a qualified Toshiba Representative who is
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from
batteries. To arrange for battery replacement, contact your nearest Toshiba authorized service center.
Misuse of this equipment could result in human injury and equipment
damage. In no event will Toshiba Corporation be responsible or liable for
either indirect or consequential damage or injury that may result from the use
of this equipment.
Do not dispose of the batteries in a fire. The batteries may explode.
Do not open or mutilate the batteries. Released electrolyte is harmful to the
eyes and skin and could also be toxic.