1600XP/XPi Series Installation and Operation Manual – 60616-012
5. Installation Precautions
NOTICE
1. Observe the following environmental restrictions:
• Install the unit in a well-ventilated location; allow at least 4 inches (10 cm) on all sides for air
ventilation and for maintenance.
• Install the unit where the ambient temperature is within the range specied in Appendix A -
“Specications”.
• DO NOT install the UPS in areas that are subject to high humidity.
• DO NOT install the UPS in areas that allow exposure to direct sunlight.
• DO NOT install the UPS in areas that allow exposure to high levels of airborne dust, metal
particles, or ammable gases.
• DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper earth ground
will reduce the effects of electrical noise and will reduce the potential for electrical shock.
• DO NOT install the UPS in areas that would allow uids or any foreign object to get inside the
UPS.
2. UPS is intended for permanent installation only. Install the unit in a stable, level and upright position
that is free of excessive vibration.
3. Follow the instructions on the unpacking label afxed to the exterior of the UPS.
4. Retain the shipping rails for use as permanent mounting of the UPS.
WARNING
This unit contains se ale d lead a cid bat terie s.
La ck of p re venta tive m ainte nan ce cou ld result
in b atte ries explod in g a nd e mittin g ga sses an d/o r
flam e. An nu al preven tative maintena nce must be
pe rformed by a n a utho rized, traine d te chnician.
WARNING
CR IT ICAL FUSE SIZ ING
Incor rect fu se replacem ent size
may result in fir e or inadeq uate
equ ipment protection.
Re pla ce only with same type
and rating of fuse.
CAUTIO N/
A TTEN TI O N
Do not di sco nne ct
whi le unit is
o pe rati ng
on battery power.
Nes pas debrancher
sous cha rg e.
Risk of electric sho ck. Do not remove cover.
. Refer servicing to qualified se rvice personnel.
N O USER SERVIC E AB LE PA RTS
INSIDE
To reduce the risk of fire or electric shock, install in a temperature and
humid ity controlled indoor area free of conductive contamina nts.
En c as utilisation en atm osphere controlee. Consulter la notice technique.
Note: Service pe rsonnel only.
Hazardous live parts inside the UPS are energized from the battery supp ly
even when the input AC power is d isconnected.
Capac itors store hazardous energy. Do not remove cover until 5 minutes
after disconnecting all sources of supp ly.
Battery b ackup time, which was factory-set at a predetermined level,
decreases gradually b etween service periods. The ba tterie s should be
replaced every three yea rs after the last servicing, the date of which is
written on the ID plate lo cated on the rea r side of the UPS unit, or in the
boxes b elow.
Date of last battery charge:
WARNING
CAUTION
Do not i n sert ba tte ry trays w i th the power o ff !
Th is uni t is desi gned for ho t chan geable batt eries!
When i nstalli ng batteries, the UPS must b e in the
onlin e or b ypass mode. Contact Toshiba
Intern ati onal Co rporation fo r further details.
6041 2
PN 51727
EXTERNAL BATTERY CABINET
The battery cabinet must have
a nominal battery voltage of
288VDC.
WARNING
DANGER/ATTENTION
Risk of electrical shock. Do not touch u ninsulated
batt ery terminals . Batteries should be serviced by
qua lified service repre se ntative only. Miswiring of
batt ery could result in ele ctrcal sh ock and/or fire.
Risque de choc electrique . Le circuit des ba tteries
nest pa s e so led e secteur. Les cosses des ba tteries
peu vent presenter une te nsion dange reuse part
rapport a la terre . Verifier avan t de to uch er.
DANGER
Batte ry fuse is always
l iv e . R i sk of ele ctr i ca l
shock. Check fuse
voltage an d discon nect
exter nal batte ries
befo re cha nging fuse.
fig 1
fig 2
1
2
3
Unpacking Instructions
P/N 48537
TYPEFORM
OUTPUT
MFD. IN U.S.A. FROM FOREIGN AN D DOMESTIC COMPONENTS
HOUSTON, TEXAS
UNINTERRUPTIBLE POWER SUPPLY
INPUT
SERIAL NO.
PN 60381
LISTED
POWER
SUPPLY
27E5
C US
EPO
14
15
16
17
EPO 1
EPO 2
RE M O TE
REMOTE
1
L1
L2 G
X1 X2
208V
120V
120V
20 8/ 2 40 V
O UTPUT
I N PUT
N
X3
G
208V
USE COPPER 90 C ONDUC TORS ON LY. REFER TO IN STRUCTION MANUAL REGARDING TIGHTENING TO RQUE OF TERMINAL BLOCKS. FACTORY WIRED FO R 2 08V INPUT.
C OM
2
3
4
5
6 7
8
11
12
13
240V
240V
RE M O TE
JUMPE R SELECTION