Recommended Wire Size and Tightening Torque For UPS Input and Output
Terminals
Minimum Wire Size and Tightening Torque of UPS Input and Output Terminals
75 & 100kVA
(USE MINIMUM 90° C INSULATED COPPER WIRING)
75kVA 100kVA
Phase: (A) (B) (C)
Input: (H1) (H2) (H3)
(N)
AWG
(H1)-(H3)
AWG
(N)
Tightening
Torque
(in-lbs.)
(L1)-(L3) (N)
AWG
(H1)-(H3)
AWG
(N)
Tightening
Torque
(in-lbs.)
(L1)-(L3) (N)
208/120 300MCM 400MCM 325 375 350MCM 700MCM 325 375
All wire sizes are per the NEC
75kVA 100kVA
Output: (L1) (L2) (L3)
(N)
AWG
(L1)-(L3)
AWG
(N)
Tightening
Torque
(in-lbs.)
(L1)-(L3) (N)
AWG
(L1)-(L3)
AWG
(N)
Tightening
Torque
(in-lbs.)
(L1)-(L3) (N)
208/120 300MCM 400MCM 325 375 350MCM 700MCM 325 375
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC
75kVA 100kVA
Input/Output (GND)
AWG Tightening Torque AWG
Tightening
Torque
(G) 2 150 in-lbs. 2 150 in-lbs.